Online Panel Model

Product Image

pH Controller & Transmitter

MODEL : pH 600 - 1

Display : 4 + 4 Digit 0.5” & 0.39” 7 Seg RED LED Display

Electrode Input: Combined Electrode with BNC Attachment

Relay Output: Relay - 1 for Setpoint - 1, Relay - 2 for Setpoint - 2 with 5A Rating

Product Details

The pH 600 - 1 series of pH Controller and Transmitter provides a reliable method of Monitoring, Controlling & Transmitting 4 - 20mA / RS 485 MODBUS RTU communication for interfacing to PLC, Data logger, HMI, etc.,. This product is suitable to measure pH in water treatment, Electrolytic water cleaning, etc.,. in chemical industries, food process, waste water treatment, electroplating industries, textile industries & neutralization process, etc., This pH Controller & Transmitter can measured using industrial combined pH sensors, temperature can be measured using temperature sensor. This pH Controller & Transmitter has many user friendly and safety features which as follows.

Model pH 600-1
Display 4 + 4 Digit 0.5” & 0.39” 7 Seg RED LED Display
Range -2 to 16 pH
Accuracy ± 0.01 pH ± 1 digit
Resolution 0.01 pH
Input Impedance >10¹² Ohms
Temperature sensor RTD - PT 100 (3 wire)
Temperature Compensation Manual / Automatic (-20.0 to +150.0ºC)
Electrode Input Combined Electrode with BNC Attachment
Set Point - 1 & 2 Two Set Point with 6 relay status selectable
Calibration / Setpoint Using Front panel soft touch key
Relay Output Relay - 1 for Setpoint - 1, Relay - 2 for Setpoint - 2 with 5A Rating
Relay Hysteresis 0 to 5 pH (user adjustable) (only for High & Low control modes)
Relay Cyclic delay 0 to 100 seconds (user adjustable) (only for High & Low control modes)
Alarm Output (optional) Inbuilt audible buzzer with front key reset
Optional Re. Tx. output Galvanically Isolated 4 - 20 mA
Optional Comm. output Isolated RS 485
Comm. Protocol MODBUS RTU
Operating Environment -10 to 50ºC / 10 to 95 % RH Non Condensing
Power Supply 90 to 270V AC / DC 50Hz
Dimension 96 x 96 x 85 mm
Cutout Dimension 92 x 92 mm
Weight 350 grams (Approx.)

Note: Due to continuous product improvements, Published specifications may change with out notice

  • Economical, easy to calibrate and setup
  • Wide range from -2 to 16 pH
  • High Accuracy
  • Programmable auto/manual temperature compensation
  • Optional galvanically isolated 4 – 20mA output
  • Very high output impedance >10¹² Ohms
  • User selectable single or 2 point calibration
  • 2 relay outputs with configurable individual H/L setting with 6 relay status
  • Optional audible inbuilt buzzer output with front key reset
  • Universal supply voltage 90 to 270V AC/DC